IF Series – Dual Fuel Fired

Package Boiler - Dual fuel fired

Stable steam pressure, high steam dryness, long life (designed for 15 years), simple operation and wide turn-down.

Summary

Nowadays, with our Multi tube Once-Through boiler, comparing to conventional fire tube and water tube boiler, it has many clear benefits to our client who needs considerable amount of steam for heating process.  One of them is its boiler efficiency of up to 98% with gas firing, the higher the boiler efficiency, the less the fuel is burnt for the same amount of steam output, this helps our client to achieve a very attractive fuel cost saving.  Secondly, its quick start up in 15 minutes (cold start) also contributes to fuel cost saving, compared to fire tube boiler which normally requires around 40 minutes to even 1 hour for cold start.

IF Series – Dual Fuel Fired Specifications

Specifications IF – Dual Fuel Fired Series
Boiler model IF-3000CVE IF-4000CVE IF-5000CVE IF-6000CVE
Equivalent evaporation (kg/h) 3,000 4,000 5,000 6,000
Actual evaporation (kg/h) 2,516 3,354 4,192 5,031
Maximum working pressure (MPa) 0.98
Heat surface (m2) 18.6 29.4
Combustion control PID continuous
Feed water control PID continuous
Used fuel Natural gas & Diesel Oil
Gas supply pressure (MPa) 0.078 ~ 0.294 (NG) 0.098 ~ 0.294 (NG)
Boiler efficiency (%) 95
Fuel consumption – Gas kg/hr 175.6 234.1 242.6 351.1
Fuel consumption – Oil (kg/h) 167.0 222.6 278.2 333.9
Feed water temperature (℃) 55 ~ 100
Holding water quantity (L) 620 990
Dry weight (kg) 5,000 7,800
Power supply AC380V, 50Hz, 3Ø

Power Capacity

Power Capacity IF – Dual Fuel Fired Series
IF-3000CVE IF-4000CVE IF-5000CVE IF-6000CVE
Forced draft fan (kW) 11 15 15 22
Feed water pump (kW) 3.0 3.0 4.0 5.5
Feed oil pump (kW) 1.5
Control panel (kW) 0.5

Typical Layout Drawing

Sales Process

Here’s how KGA help with your solution. 

Consultation

We’ll help you to size and design the right energy solution according to your needs.

Installation

We’ll work with qualified local partner for the cost-effective installation.

We’re always available to support the necessary services.